Technical Specifications For Structural Adaptability Of High Voltage Disconnect Switchgear
In the layout of substation electrical equipment, the mechanical compatibility of switchgear and cabinet structure directly affects operational reliability. The core of the integrated design of the High Voltage Disconnect Switch switchgear and receiving cabinet lies in the coordination of structural response under dynamic operating conditions. A three-dimensional spatial interference verification model needs to be established for project implementation.
The mechanical operating characteristics of high-voltage disconnect switches determine installation constraints. The peak operating torque of a 550kV GIS rotary disconnect switch (≥2500 N·m) far exceeds that of conventional 40.5kV equipment (≤800 N·m). The yield strength of the cabinet steel plate (≥355 MPa), the resonant frequency of the seismic bracing (avoiding the 2-15Hz frequency band), and the lateral deflection limit of the insulating tie rod (≤0.5 mm/m) together constitute the basis of the integration technology. Selection should refer to the operating force spectrum data of IEC 62271-102 Annex F.
Static installation is only a basic requirement. The dynamic adaptation mechanism includes triple verification: a design to avoid the impact force of switch opening and closing and the natural frequency of the cabinet (Δf≥3Hz), a compensation gap for the thermal expansion displacement of the busbar (4.2mm reserved per meter), and an electromagnetic compatibility distance under VFTO overvoltage (≥1.5×phase spacing). On-site operating parameters (such as short-circuit current transient electrodynamics, equipment foundation settlement rate, and daily fluctuation amplitude of ambient temperature) directly determine the structural safety margin.