Principle Of Graded Matching Of Drop-out Fuses

Date: | Read: 39

According to GB/T 15166 standard, the drop out fuse rated current should be selected according to the following principles:

1. Distribution transformer capacity ≤100kVA: select 1.5 times the transformer rated current.

2. When the capacity is in the range of 100kVA<capacity≤315kVA, it is advisable to select 2.0 - 2.5 times the rated current.

3. Capacity>315kVA: Short-circuit current calculation is required and relay protection is coordinated.