Installation Angle Of Drop-out Fuse
Date: | Read: 2
The axis of the melting tube is at an angle of 25°±2° to the vertical line to ensure that the drop out fuse fuse can complete the falling action within 0.3 seconds after the fuse is blown. An inclination deviation exceeding ±5° will result in a delay of ≥0.5 seconds.